Liquid leak tightness isn't optional. It's mandatory.

large-computer-room_small.jpg

Advanced Cooling Infrastructure for Modern Data Centers

The shift to AI workloads and dense GPU clusters is putting unprecedented strain on data center cooling. Conventional approaches, such as air-cooled servers, are no longer able to handle the thermal load from high-performance computing (HPC) workloads.

The stakes of a cooling failure are high. A single undetected leak can trigger:

  • Unplanned downtime
  • Damaged equipment
  • Escalating repair and remediation costs

The earlier a leak is detected, the lower the risk.

As facilities increasingly turn to liquid cooling to manage these demands, catching fluid loss and thermal issues before they escalate is what keeps operations reliable.

Proactive leak testing at the manufacturing site is the most reliable way to ensure that the components in your technology cooling system (TCS) loop remain leak-free throughout the equipment lifecycle.

We bring deep leak testing expertise to the critical components inside both air and liquid cooling systems, helping operators protect uptime and hardware from day one.

INFICON looks forward to partnering with you – for leak-free cooling, today and beyond.

Failure Points in a Data Center

These are some common failure points in a data center.
Data center Interactive Image
Datacenter Interactive Image Universal quick disconnect coupling

Rack Manifolds

Separate supply (cold) and return (hot) manifolds route coolant through the rack. Leak-tight hoses, precision crimps, and specialized quick-disconnect couplings keep coolant away from the electronics inside the server and prevent fluid loss at the connections to the cold plates. O-rings on the manifold are also common points of potential fluid leakage. Typical leak rates are around 10⁻⁵ mbar·l/s.

Data center Interactive Image Cold plate

Cold Plates

Cold plates sit directly on the processors. A leak can cause electrical shorts, board damage, overheating and corrosion. Small leaks grow over time into larger leaks on the outer walls. Leak detection at welds, seams and fittings finds micro-leaks before they become failures. Cold plates are therefore held to the tightest leak rates in the range 10-5 to 10⁻6 mbar·l/s.

Data center Interactive Image CDU

Coolant Distribution Unit (CDU)

A leak-tight CDU protects the loop from coolant loss and unplanned downtime. Every part that carries or contains coolant is a potential leak path, including pumps, heat exchanger, piping, valves and other critical components.
To meet strict tightness requirements, modern CDUs are leak tested to an acceptance limit of 10⁻⁵ mbar·l/s.

Datacenter Interactive Image Supply and Return Pipings

Supply and Return Piping

Leak-free welds, flanges and valves along lengthy pipe runs prevent small leaks from becoming major coolant loss or damage to the building and equipment, when tested to typical leak rates of 10⁻⁵ mbar·l/s.

Heat Exchanger (inside CDU)

Leak-tight gaskets, brazed joints, and plates prevent coolant loss and unwanted mixing between the primary and secondary loops. Typical leak rates are around 10⁻⁵ mbar·l/s.

Universal quick disconnect coupling 3

Quick Disconnect Couplings (QDCs)

QDCs are a standard mechanical interface in liquid cooling circuits, allowing components to be disconnected with minimal leakage. Because the coolant is electrically conductive, leaks can cause coolant loss or short circuits. QDCs are often tested during manufacturing for leak rates in the range of 10-5 to10-6 mbar∙l/s.

Datacenter Interactive Image Universal quick disconnect coupling

Separate supply (cold) and return (hot) manifolds route coolant through the rack. Leak-tight hoses, precision crimps, and specialized quick-disconnect couplings keep coolant away from the electronics inside the server and prevent fluid loss at the connections to the cold plates. O-rings on the manifold are also common points of potential fluid leakage. Typical leak rates are around 10⁻⁵ mbar·l/s.

Data center Interactive Image Cold plate

Cold plates sit directly on the processors. A leak can cause electrical shorts, board damage, overheating and corrosion. Small leaks grow over time into larger leaks on the outer walls. Leak detection at welds, seams and fittings finds micro-leaks before they become failures. Cold plates are therefore held to the tightest leak rates in the range 10-5 to 10⁻6 mbar·l/s.

Data center Interactive Image CDU

A leak-tight CDU protects the loop from coolant loss and unplanned downtime. Every part that carries or contains coolant is a potential leak path, including pumps, heat exchanger, piping, valves and other critical components.
To meet strict tightness requirements, modern CDUs are leak tested to an acceptance limit of 10⁻⁵ mbar·l/s.

Datacenter Interactive Image Supply and Return Pipings

Leak-free welds, flanges and valves along lengthy pipe runs prevent small leaks from becoming major coolant loss or damage to the building and equipment, when tested to typical leak rates of 10⁻⁵ mbar·l/s.

Leak-tight gaskets, brazed joints, and plates prevent coolant loss and unwanted mixing between the primary and secondary loops. Typical leak rates are around 10⁻⁵ mbar·l/s.

Universal quick disconnect coupling 3

QDCs are a standard mechanical interface in liquid cooling circuits, allowing components to be disconnected with minimal leakage. Because the coolant is electrically conductive, leaks can cause coolant loss or short circuits. QDCs are often tested during manufacturing for leak rates in the range of 10-5 to10-6 mbar∙l/s.

Liquid leak tightness isn't optional. It's mandatory.

Leaks cause downtime, hardware damage, and data loss in your data center.
Contact Us
Which Cooling Method are you Interested in?

 

We offer modern, proactive leak detection solutions for quality tests on a variety of cooling components throughout the entire loop—from production and rework to assembled systems.

Direct to Chip Cooling (Single-phase and Two-phase)
  • Cold plates
  • Hoses
  • CDU (Coolant Distribution Unit)
  • QDC (Quick Disconnect Couplings)
  • Condensers
  • Piping
Rear Door Heat Exchangers
  • Coils
  • Compressor
  • Piping
CRAC/CRAH
  • Coils
  • Compressor 
  • Valves
  • Piping
  • Refrigerant circuits
Immersion (Single-phase and Two-phase)
  • Tank seams and seals
  • Pumps
  • Boiling chambers
  • Brazed joints
  • Condensers

INFICON—Your Trusted Partner in Leak Detection

INFICON has decades of experience partnering with cooling component and air- & liquid-cooling manufacturers and chiller/CRAH/CRAC OEMs worldwide.

  • Global provider of leak detection solutions meeting the strictest industry standards
  • Expertise in tracer-gas leak detection (He, H₂, Ar, refrigerants)
  • Trusted by industries with zero tolerance for leaks: HVAC-R, automotive, semiconductor
  • Offers application support for all modern cooling methods

Download Free Whitepaper