;====================================================== ; HPG400 - SP with Profibus SEMI Profile Option ; ; INFICON AG ; Alte Landstrasse 6 ; FL - 9496 Balzers ; Principality of Liechtenstein ; Contact: Rolf Enderes / R&D ; Phone: + 423 / 388 3264 ; Version: V1.0 ;====================================================== #Profibus_DP ;General parameters GSD_Revision = 2 Vendor_Name = "Inficon" Model_Name = "HPG400-SP" Revision = "V1.0" Ident_Number = 0x06A8 Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release= "1.0" Software_Release= "1.0" 9.6_supp = 1 19.2_supp = 1 45.45_supp = 1 93.75_supp = 1 187.5_supp = 1 500_supp = 1 1.5M_supp = 1 3M_supp = 1 6M_supp = 1 12M_supp = 1 MaxTsdr_9.6 = 60 MaxTsdr_19.2 = 60 MaxTsdr_45.45 = 250 MaxTsdr_93.75 = 60 MaxTsdr_187.5 = 60 MaxTsdr_500 = 100 MaxTsdr_1.5M = 150 MaxTsdr_3M = 250 MaxTsdr_6M = 450 MaxTsdr_12M = 800 Redundancy = 0 24V_Pins = 0 ; Slave-Specification: Freeze_Mode_supp = 0 Sync_Mode_supp = 0 Set_Slave_Add_Supp = 0 Auto_Baud_supp = 1 Min_Slave_Intervall = 100 Fail_Safe = 0 Modul_Offset = 0 Slave_Family = 0 Modular_Station = 1 Max_Module = 1 Max_Input_len = 15 Max_Output_len = 10 Max_Data_len = 25 Max_Diag_Data_Len = 25 ; UserPrmData: Length: Please select the Dataunit you want to use for cyclic data transfer User_Prm_Data_Len=5 ;User_Prm_Data=0x00,0x00,0x00,0x03,0xe9 ;Counts User_Prm_Data=0x00,0x00,0x00,0x05,0x1c ;mbar ;User_Prm_Data=0x00,0x00,0x00,0x05,0x15 ;Torr ;User_Prm_Data=0x00,0x00,0x00,0x05,0x16 ;Micron ;User_Prm_Data=0x00,0x00,0x00,0x05,0x1D ;Pascal ; DPV1 Slave related keywords DPV1_Slave = 1 C1_Read_Write_supp = 1 C2_Read_Write_supp = 1 C1_Max_Data_Len = 240 C2_Max_Data_Len = 240 C1_Response_Timeout = 400 C2_Response_Timeout = 400 C1_Read_Write_required = 0 C2_Read_Write_required = 0 C2_Max_Count_Channels = 3 Max_Initiate_PDU_Length = 52 Diagnostic_Alarm_supp = 0 Process_Alarm_supp = 0 Pull_Plug_Alarm_supp = 0 Status_Alarm_supp = 0 Update_Alarm_supp = 0 Manufacturer_Specific_Alarm_supp = 0 Extra_Alarm_SAP_supp = 0 Alarm_Sequence_Mode_Count = 0 Alarm_Type_Mode_supp = 0 DPV1_Data_Types = 0 WD_Base_1ms_supp = 0 Check_Cfg_Mode = 0 Ident_Maintenance_supp = 1 ; Module Definition List ; ; Abbreviations: ; ExS - ExceptionStatus ; PI - ParameterChannelIn ; PO - ParameterChannelOut ; PVF - ProcessValue Float ; PVI - ProcessValue Interger16 ; PVSl - OneofNPVSelector ; TCd - TranstionCommand ; TCdV - TranstionCommandValue ; TpS - TripStatus ; ; Modules without Parameter Cannel Module="ExS,TpS,PVSl,PVI" 0x44, 0x84, 0x05, 0x05, 0x05, 0x03 EndModule Module="ExS,TpS,PVSl,PVF" 0x44, 0x86, 0x05, 0x05, 0x05, 0x08 EndModule ; Modules with Parameter Cannel Module="PO,PI,ExS,TpS,PVSl,PVI" 0xC6, 0x87, 0x8C, 0x0A, 0x0A, 0x05, 0x05, 0x05, 0x03 EndModule Module="PO,PI,ExS,TpS,PVSl,PVF" 0xC6, 0x87, 0x8E, 0x0A, 0x0A, 0x05, 0x05, 0x05, 0x08 EndModule